Ultrasonic Meter Type
BTU Meter / Flow Meter, District
uFlow 230 SERIES
1. Introduction
The uFlow 230 series ultrasonic BTU meter can be used for measuring the energy consumption in heat / cooling application for billing purpose. The measurement principle is static and based on the measurement of transit time with pair of ultrasonic transducer propagating at each other upstream and downstream. All calculation and flow measurement circuits are designed on one circuit board, thus offering exceptional accuracy and reality.
2. Features
- High capacity 3.6 lithium battery inside, above 8 till 10 years shelf life
- Dynamic range of 250:1, 100:1, 50:1
- Can be mounted in flow pipe or return pipe, and can be mounted horizontally or vertically
- Support optical, RS485 and wired & wireless M-bus interface, convenient for user to manage data in different manners
- Complies to Modbus RTU and EN13757 communication protocol
- Certified by CMC and MID
- Advanced calibrating device, adopt international advanced automatic heat meter calibration device, ensure the product accuracy
- Can be used as cooling, heat or combined climatic meter
3. Application
- Green building management
- Tenant billing
- Energy management
4. Dimensions
Nominal Diameter (mm) | 50 | 65 | 80 | 100 | |
Nominal Flow Rate : qp (m³/h) | 15 | 25 | 40 | 60 | |
Dimension (mm) | L | 200/270 | 200/300 | 225/300 | 250/360 |
D | 165 | 185 | 200 | 220 | |
H | 247 | 258 | 279 | 299 | |
K | 125 | 145 | 160 | 180 | |
N x ФL |
4 x Ф18 |
4 x Ф18 |
8 x Ф18 |
8 x Ф18 |
|
Weight (kg) | 8 | 9 | 12 | 15 | |
Channel | Single of Bi-channel optional | ||||
Pressure Loss (kPa/qp) | 4 | 6 | 9 | 11 | |
Working Pressure | 1.6MPa (2.5MPa can be customized upon request) |
5. Technical Specification
SPECIFICATIONS – Calculator | |
---|---|
Display |
LCD, 8 digits Energy, power, volume, temperature, flow rate |
Cummulative heat energy: KWh or MJ (display range: 0~9999999.9), Thermal power: KW | |
Instantaneous flow: m³/h, cumulative volume:m³, Supply water temperature: °C. Return water temperature: °C, Temperature difference, Total operating time | |
Approval |
MID |
Language | English |
Ambient Storage Temperature |
A Class (5~55) °C or B Class (-25~55)°C optional |
Temperature Measuring Range |
4-95°C, 130°C can be customized |
Temperature Sensor |
PT1000 (PT500, PT100 can be customized) |
Cable Length of Temperature Sensor |
1.3 meters |
Power Supply |
3.6V lithium battery |
Battery Lifetime |
≥10 years |
Installation |
Horizontal or vertical |
Communication |
Modbus, M-bus, optical, pulse |
IP Rating |
IP67 |
Accuracy |
Class 2 |
Mounting Position |
Vertical or horizontal |
TECHNICAL PARAMETER | |
---|---|
Flow Velocity |
0.1 ~ 7m/s |
0.15~12m/s (need to be customized) |
|
Maximum Volume |
999999.99 |
Maximum Heat |
999999999 |